Air Ducts and Air Connectors Installation Instructions
CONNECTIONS      SPLICES
1. After desired length is determined, cut completely around and through duct with knife or scissors. Cut wire with wire
cutters. 1. Peel back jacket and insulation from core. Butt two cores together on a standard 4" [100 mm] metal sleeve.

  
2. Pull back jacket and insulation from core. Slide at least 1" [25 mm] of core over collar, pipe or fitting. Tape core with at
least 2 wraps of duct tape. Secure with clamp. 2. Tape cores together with at least 2 wraps of duct tape. Secure with 2
clamps.  

  
3. Pull jacket and insulation back over core. Tape jacket with at least 2 wraps of duct tape. A clamp may be used in
place of or in combination with the duct tape. 3. Pull jacket and insulation back over cores. Tape jackets together with at
least 2 wraps of duct tape.  

      
NOTES:
1. For un insulated air ducts and air connectors, disregard references to insulation and jacket.
2. Use beaded fittings for pressures exceeding 2" w.g. [500 Pa] and for diameters 12" [300 mm] and larger.
3. Use tapes listed and labeled in accordance with Standard UL 181B and marked "181B-FX".
4. Use clamps as specified on manufacturer's UL 181 Installation Instructions.
Duct Board
Fiberglass Duct Board
Used to fabricate components for heating and cooling duct systems
Assured thermal performance
Acoustically efficient
Lightweight
Virtually eliminates air leakage

Fiberglass Duct Board is used to fabricate components for indoor commercial and residential heating, ventilating and
air conditioning duct system operating at static pressures to +/- 2in.